| Len | Scala | Endian | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 2 | Total-instantaneous-real-power-(3-phase-total) Total-instantaneous-real-power-(3-phase-total) | total_instantaneous_real_power_3_phase_total | 3 | uint16 | 1 | 1 | kW | R | — | |
| 3 | Total-instantaneous-reactive-power-(3-phase-total) Total-instantaneous-reactive-power-(3-phase-total) | total_instantaneous_reactive_power_3_phase_total | 3 | uint16 | 1 | 1 | kVAR | R | — | |
| 4 | Total-instantaneous-apparent-power-(3-phase-total) Total-instantaneous-apparent-power-(3-phase-total) | total_instantaneous_apparent_power_3_phase_total | 3 | uint16 | 1 | 1 | kVA | R | — | |
| 5 | Total-power-factor-(total-kw-/-total-kva) Total-power-factor-(total-kw-/-total-kva) | total_power_factor_total_kw_total_kva | 3 | uint16 | 1 | 1 | Ratio | R | — | |
| 6 | Voltage,-line-to-line,-average-of-phases Voltage,-line-to-line,-average-of-phases | voltage_line_to_line_average_of_phases | 3 | uint16 | 1 | 1 | Volt | R | — | |
| 7 | Voltage,-line-to-neutral,-average-of-phases Voltage,-line-to-neutral,-average-of-phases | voltage_line_to_neutral_average_of_phases | 3 | uint16 | 1 | 1 | Volt | R | — | |
| 8 | Current,-average-of-phases Current,-average-of-phases | current_average_of_phases | 3 | uint16 | 1 | 1 | Amp | R | — | |
| 9 | Real-power,-L1 Real-power,-L1 | real_power_l1 | 3 | uint16 | 1 | 1 | kW | R | — | |
| 10 | Real-power,-L2 Real-power,-L2 | real_power_l2 | 3 | uint16 | 1 | 1 | kW | R | — | |
| 11 | Real-power,-L3 Real-power,-L3 | real_power_l3 | 3 | uint16 | 1 | 1 | kW | R | — | |
| 12 | Power-factor,-L1 Power-factor,-L1 | power_factor_l1 | 3 | uint16 | 1 | 1 | Ratio | R | — | |
| 13 | Power-factor,-L2 Power-factor,-L2 | power_factor_l2 | 3 | uint16 | 1 | 1 | Ratio | R | — | |
| 14 | Power-factor,-L3 Power-factor,-L3 | power_factor_l3 | 3 | uint16 | 1 | 1 | Ratio | R | — | |
| 15 | Voltage,-L1-L2 Voltage,-L1-L2 | voltage_l1_l2 | 3 | uint16 | 1 | 1 | Volt | R | — | |
| 16 | Voltage,-L2-L3 Voltage,-L2-L3 | voltage_l2_l3 | 3 | uint16 | 1 | 1 | Volt | R | — | |
| 17 | Voltage,-L3-L1 Voltage,-L3-L1 | voltage_l3_l1 | 3 | uint16 | 1 | 1 | Volt | R | — | |
| 18 | Voltage,-L1-N Voltage,-L1-N | voltage_l1_n | 3 | uint16 | 1 | 1 | Volt | R | — | |
| 19 | Voltage,-L2-N Voltage,-L2-N | voltage_l2_n | 3 | uint16 | 1 | 1 | Volt | R | — | |
| 20 | Voltage,-L3-N Voltage,-L3-N | voltage_l3_n | 3 | uint16 | 1 | 1 | Volt | R | — | |
| 21 | Current,-instantaneous,-L1 Current,-instantaneous,-L1 | current_instantaneous_l1 | 3 | uint16 | 1 | 1 | Amp | R | — | |
| 22 | Current,-instantaneous,-L2 Current,-instantaneous,-L2 | current_instantaneous_l2 | 3 | uint16 | 1 | 1 | Amp | R | — | |
| 23 | Current,-instantaneous,-L3 Current,-instantaneous,-L3 | current_instantaneous_l3 | 3 | uint16 | 1 | 1 | Amp | R | — | |
| 24 | Present-demand-sub-interval Present-demand-sub-interval | present_demand_sub_interval | 3 | uint16 | 1 | 1 | kW | R | — | |
| 25 | Minimum-demand Minimum-demand | minimum_demand | 3 | uint16 | 1 | 1 | kW | R | — | |
| 26 | Maximum-demand Maximum-demand | maximum_demand | 3 | uint16 | 1 | 1 | kW | R | — | |
| 27 | Present-demand Present-demand | present_demand | 3 | uint16 | 1 | 1 | kW | R | — | |
| 28 | Peak-demand Peak-demand | peak_demand | 3 | uint16 | 1 | 1 | kW | R | — | |
| 30 | Ct-size-(100,-300,-etc.) Ct-size-(100,-300,-etc.) | ct_size_100_300_etc | 3 | uint16 | 1 | 1 | Amps | R | — | |
| 31 | Count-of-kwh-resets Count-of-kwh-resets | count_of_kwh_resets | 3 | uint16 | 1 | 1 | Count | R | — | |
| 32 | Count-of-peak-demand-resets Count-of-peak-demand-resets | count_of_peak_demand_resets | 3 | uint16 | 1 | 1 | Count | R | — | |
| 33 | Count-of-sub-intervals Count-of-sub-intervals | count_of_sub_intervals | 3 | uint16 | 1 | 1 | Count | R | — | |
| 34 | Count-of-number-readings-in-present-sub-interval Count-of-number-readings-in-present-sub-interval | count_of_number_readings_in_present_sub_interval | 3 | uint16 | 1 | 1 | Count | R | — | |
| 35 | System-type:-see-manual System-type:-see-manual | system_type_see_manual | 3 | uint16 | 1 | 1 | integer | R | — | |
| 36 | Sub-interval-length:-sets-the-length-of-a-sub-interval.-value-is-the-number-of-seconds-times-5-(for-example,-15-minutes-is-4500).-for-sync-to-comms,-set-this-to-zero Sub-interval-length:-sets-the-length-of-a-sub-interval.-value-is-the-number-of-seconds-times-5-(for-example,-15-minutes-is-4500).-for-sync-to-comms,-set-this-to-zero | sub_interval_length_sets_the_length_of_a_sub_interval_value_is_the_number_of_seconds_times_5_for_example_15_minutes_is_4500_for_sync_to_comms_set_this_to_zero | 3 | uint16 | 1 | 1 | integer | R | — | |
| 37 | Number-of-sub-intervals-per-demand-interval.-sets-the-number-of-sub-intervals-that-make-a-single-demand-interval.-legal-values-are-1-to-6.-for-block-demand,-set-this-to-1 Number-of-sub-intervals-per-demand-interval.-sets-the-number-of-sub-intervals-that-make-a-single-demand-interval.-legal-values-are-1-to-6.-for-block-demand,-set-this-to-1 | number_of_sub_intervals_per_demand_interval_sets_the_number_of_sub_intervals_that_make_a_single_demand_interval_legal_values_are_1_to_6_for_block_demand_set_this_to_1 | 3 | uint16 | 1 | 1 | integer | R | — | |
| 38 | Command Command | command | 3 | uint16 | 1 | 1 | bit map | R | — | |
| 256 | Real-energy-consumption Real-energy-consumption | real_energy_consumption | 3 | float32 | 2 | 1 | kWh | R | — | |
| 258 | Real-energy-consumption-(redundant) Real-energy-consumption-(redundant) | real_energy_consumption_redundant | 3 | float32 | 2 | 1 | kWh | R | — | |
| 260 | Total-instantaneous-real-power Total-instantaneous-real-power | total_instantaneous_real_power | 3 | float32 | 2 | 1 | kW | R | — | |
| 262 | Total-instantaneous-reactive-power Total-instantaneous-reactive-power | total_instantaneous_reactive_power | 3 | float32 | 2 | 1 | kVAR | R | — | |
| 264 | Total-instantaneous-apparent-power Total-instantaneous-apparent-power | total_instantaneous_apparent_power | 3 | float32 | 2 | 1 | kVA | R | — | |
| 266 | Total-power-factor-(total-kw-/-total-kva) Total-power-factor-(total-kw-/-total-kva) | total_power_factor_total_kw_total_kva_266 | 3 | float32 | 2 | 1 | Ratio | R | — | |
| 268 | Voltage,-line-to-line,-average-of-3-phases Voltage,-line-to-line,-average-of-3-phases | voltage_line_to_line_average_of_3_phases | 3 | float32 | 2 | 1 | Volt | R | — | |
| 270 | Voltage,-line-to-neutral,-average-of-3-phases Voltage,-line-to-neutral,-average-of-3-phases | voltage_line_to_neutral_average_of_3_phases | 3 | float32 | 2 | 1 | Volt | R | — | |
| 272 | Current,-average-of-3-phases Current,-average-of-3-phases | current_average_of_3_phases | 3 | float32 | 2 | 1 | Amp | R | — | |
| 274 | Real-power,-L1 Real-power,-L1 | real_power_l1_274 | 3 | float32 | 2 | 1 | kW | R | — | |
| 276 | Real-power,-L2 Real-power,-L2 | real_power_l2_276 | 3 | float32 | 2 | 1 | kW | R | — | |
| 278 | Real-power,-L3 Real-power,-L3 | real_power_l3_278 | 3 | float32 | 2 | 1 | kW | R | — | |
| 280 | Power-factor,-L1 Power-factor,-L1 | power_factor_l1_280 | 3 | float32 | 2 | 1 | Ratio | R | — | |
| 282 | Power-factor,-L2 Power-factor,-L2 | power_factor_l2_282 | 3 | float32 | 2 | 1 | Ratio | R | — |
Leggi questi registri via API
curl https://busbabel.vercel.app/api/devices/schneider/electric-em4200/registers?version=v1