Importata da documento

Mappa registri Modbus

50 registri

LenScalaEndian
2
Total-instantaneous-real-power-(3-phase-total)
Total-instantaneous-real-power-(3-phase-total)
total_instantaneous_real_power_3_phase_total3uint1611kWR
3
Total-instantaneous-reactive-power-(3-phase-total)
Total-instantaneous-reactive-power-(3-phase-total)
total_instantaneous_reactive_power_3_phase_total3uint1611kVARR
4
Total-instantaneous-apparent-power-(3-phase-total)
Total-instantaneous-apparent-power-(3-phase-total)
total_instantaneous_apparent_power_3_phase_total3uint1611kVAR
5
Total-power-factor-(total-kw-/-total-kva)
Total-power-factor-(total-kw-/-total-kva)
total_power_factor_total_kw_total_kva3uint1611RatioR
6
Voltage,-L-l,-average-of-3-phases
Voltage,-L-l,-average-of-3-phases
voltage_l_l_average_of_3_phases3uint1611VoltR
7
Voltage,-L-n,-average-of-3-phases
Voltage,-L-n,-average-of-3-phases
voltage_l_n_average_of_3_phases3uint1611VoltR
8
Current,-average-of-3-phases
Current,-average-of-3-phases
current_average_of_3_phases3uint1611AmpR
9
Real-power,-phase-A
Real-power,-phase-A
real_power_phase_a3uint1611kWR
10
Real-power,-phase-B
Real-power,-phase-B
real_power_phase_b3uint1611kWR
11
Real-power,-phase-C
Real-power,-phase-C
real_power_phase_c3uint1611kWR
12
Power-factor,-phase-A
Power-factor,-phase-A
power_factor_phase_a3uint1611RatioR
13
Power-factor,-phase-B
Power-factor,-phase-B
power_factor_phase_b3uint1611RatioR
14
Power-factor,-phase-C
Power-factor,-phase-C
power_factor_phase_c3uint1611RatioR
15
Voltage,-phase-A-B
Voltage,-phase-A-B
voltage_phase_a_b3uint1611VoltR
16
Voltage,-phase-B-C
Voltage,-phase-B-C
voltage_phase_b_c3uint1611VoltR
17
Voltage,-phase-A-C
Voltage,-phase-A-C
voltage_phase_a_c3uint1611VoltR
18
Voltage,-phase-A-N
Voltage,-phase-A-N
voltage_phase_a_n3uint1611VoltR
19
Voltage,-phase-B-N
Voltage,-phase-B-N
voltage_phase_b_n3uint1611VoltR
20
Voltage,-phase-C-N
Voltage,-phase-C-N
voltage_phase_c_n3uint1611VoltR
21
Current,-instantaneous,-phase-A
Current,-instantaneous,-phase-A
current_instantaneous_phase_a3uint1611AmpR
22
Current,-instantaneous,-phase-B
Current,-instantaneous,-phase-B
current_instantaneous_phase_b3uint1611AmpR
23
Current,-instantaneous,-phase-C
Current,-instantaneous,-phase-C
current_instantaneous_phase_c3uint1611AmpR
25
Frequency-(derived-from-phase-a)
Frequency-(derived-from-phase-a)
frequency_derived_from_phase_a3uint1611HzR
26
Apparent-energy-consumption-(msr)
Apparent-energy-consumption-(msr)
apparent_energy_consumption_msr3uint3221KVAhR
28
Reactive-energy-consumption-(msr)
Reactive-energy-consumption-(msr)
reactive_energy_consumption_msr3uint3221KVARhR
30
Apparent-power,-phase-A
Apparent-power,-phase-A
apparent_power_phase_a3uint1611kVAR
31
Apparent-power,-phase-B
Apparent-power,-phase-B
apparent_power_phase_b3uint1611kVAR
32
Apparent-power,-phase-C
Apparent-power,-phase-C
apparent_power_phase_c3uint1611kVAR
33
Reactive-power,-phase-A
Reactive-power,-phase-A
reactive_power_phase_a3uint1611kVARR
34
Reactive-power,-phase-B
Reactive-power,-phase-B
reactive_power_phase_b3uint1611kVARR
35
Reactive-power,-phase-C
Reactive-power,-phase-C
reactive_power_phase_c3uint1611kVARR
36
Total-real-power-present-demand
Total-real-power-present-demand
total_real_power_present_demand3uint1611kWR
37
Total-reactive-power-present-demand
Total-reactive-power-present-demand
total_reactive_power_present_demand3uint1611kVARR
38
Total-apparent-power-present-demand
Total-apparent-power-present-demand
total_apparent_power_present_demand3uint1611kVAR
39
Total-real-power-max.-demand
Total-real-power-max.-demand
total_real_power_max_demand3uint1611kWR
40
Total-reactive-power-max.-demand
Total-reactive-power-max.-demand
total_reactive_power_max_demand3uint1611kVARR
41
Total-apparent-power-max.-demand
Total-apparent-power-max.-demand
total_apparent_power_max_demand3uint1611kVAR
42
Pulse-counter-1-(real-energy)
Pulse-counter-1-(real-energy)
pulse_counter_1_real_energy3uint3221R
44
Pulse-counter-2-(reactive-energy)
Pulse-counter-2-(reactive-energy)
pulse_counter_2_reactive_energy3uint3221R
46
Real-energy-consumption-phase-A
Real-energy-consumption-phase-A
real_energy_consumption_phase_a3uint3221kWhR
48
Real-energy-consumption-phase-B
Real-energy-consumption-phase-B
real_energy_consumption_phase_b3uint3221kWhR
50
Real-energy-consumption-phase-C
Real-energy-consumption-phase-C
real_energy_consumption_phase_c3uint3221kWhR
129
Single-phase:-A-+-N
Single-phase:-A-+-N
single_phase_a_n3uint1611R
130
Ct-ratio-primary
Ct-ratio-primary
ct_ratio_primary3uint1611AmpsR
131
Ct-ratio-secondary-interface-(1-or-1/3-v,-may-not-be-user-configurable)
Ct-ratio-secondary-interface-(1-or-1/3-v,-may-not-be-user-configurable)
ct_ratio_secondary_interface_1_or_1_3_v_may_not_be_user_configurable3uint1611R
132
Pt-ratio:-the-meter-scales-this-value-by-100-(i.e.-entering-200-yields-a-potential-transformer-ratio-of-2:1).-the-default-is-100-(1.00:1),-which-is-with-no-pt-attached.-set-this-value-before-setting-the-system-voltage-(below)
Pt-ratio:-the-meter-scales-this-value-by-100-(i.e.-entering-200-yields-a-potential-transformer-ratio-of-2:1).-the-default-is-100-(1.00:1),-which-is-with-no-pt-attached.-set-this-value-before-setting-the-system-voltage-(below)
pt_ratio_the_meter_scales_this_value_by_100_i_e_entering_200_yields_a_potential_transformer_ratio_of_2_1_the_default_is_100_1_00_1_which_is_with_no_pt_attached_set_this_value_before_setting_the_system_voltage_below3uint1611R
133
System-voltage:-this-voltage-is-line-to-line,-except-for-system-type-10-which-is-line-to-neutral.-the-meter-uses-this-value-to-calculate-the-full-scale-power-for-the-analog-outputs-and-pulse-configuration-(below),-and-as-full-scale-for-phase-loss-(register-142).-the-meter-will-refuse-voltages-that-are-outside-the-range-of-82-660-volts-when-divided-by-the-pt-ratio-(above)
System-voltage:-this-voltage-is-line-to-line,-except-for-system-type-10-which-is-line-to-neutral.-the-meter-uses-this-value-to-calculate-the-full-scale-power-for-the-analog-outputs-and-pulse-configuration-(below),-and-as-full-scale-for-phase-loss-(register-142).-the-meter-will-refuse-voltages-that-are-outside-the-range-of-82-660-volts-when-divided-by-the-pt-ratio-(above)
system_voltage_this_voltage_is_line_to_line_except_for_system_type_10_which_is_line_to_neutral_the_meter_uses_this_value_to_calculate_the_full_scale_power_for_the_analog_outputs_and_pulse_configuration_below_and_as_full_scale_for_phase_loss_register_142_the_meter_will_refuse_voltages_that_are_outside_the_range_of_82_660_volts_when_divided_by_the_pt_ratio_above3uint1611R
134
Theoretical-maximum-system-power:-this-read-only-value-is-the-theoretical-maximum-power-the-meter-can-expect-to-see-on-a-service.-this-value-is-100%-of-scale-on-the-analog-output-(0-5-vdc-or-4-20-ma),-if-equipped.-the-meter-recalculates-this-value-if-the-user-changes-the-ct-size,-system-type,-or-system-voltage.-this-integer-value-has-the-same-scale-as-other-integer-power-registers-(see-register-140-for-power-scaling)
Theoretical-maximum-system-power:-this-read-only-value-is-the-theoretical-maximum-power-the-meter-can-expect-to-see-on-a-service.-this-value-is-100%-of-scale-on-the-analog-output-(0-5-vdc-or-4-20-ma),-if-equipped.-the-meter-recalculates-this-value-if-the-user-changes-the-ct-size,-system-type,-or-system-voltage.-this-integer-value-has-the-same-scale-as-other-integer-power-registers-(see-register-140-for-power-scaling)
theoretical_maximum_system_power_this_read_only_value_is_the_theoretical_maximum_power_the_meter_can_expect_to_see_on_a_service_this_value_is_100_of_scale_on_the_analog_output_0_5_vdc_or_4_20_ma_if_equipped_the_meter_recalculates_this_value_if_the_user_changes_the_ct_size_system_type_or_system_voltage_this_integer_value_has_the_same_scale_as_other_integer_power_registers_see_register_140_for_power_scaling3uint1611kWR
136
Display-units:-0-=-iec-(u,-v,-p,-q,-s),-1-=-ieee-(default:-vll,-vln,-w,-var,-va)
Display-units:-0-=-iec-(u,-v,-p,-q,-s),-1-=-ieee-(default:-vll,-vln,-w,-var,-va)
display_units_0_iec_u_v_p_q_s_1_ieee_default_vll_vln_w_var_va3uint1611R
137
Scale-factors-note:-these-registers-contain-a-signed-integer-that-scales-the-corresponding-integer-registers.-floating-point-registers-are-not-scaled.-scaling-is-recalculated-when-the-meter-configuration-is-changed
Scale-factors-note:-these-registers-contain-a-signed-integer-that-scales-the-corresponding-integer-registers.-floating-point-registers-are-not-scaled.-scaling-is-recalculated-when-the-meter-configuration-is-changed
scale_factors_note_these_registers_contain_a_signed_integer_that_scales_the_corresponding_integer_registers_floating_point_registers_are_not_scaled_scaling_is_recalculated_when_the_meter_configuration_is_changed3int1611R

Leggi questi registri via API