Daikin Applied Pathfinder AWV Chiller
Pathfinder AWV Chiller
Daikin Applied Pathfinder AWV Chiller (hvac) ha una mappa Modbus di 96 registri, riferita al firmware AWV application software 263220504 (document baseline); individual points need 263220112 / 263220502. Function code usati: 3 (holding register). Tipi di dato: int16, string, uint16, uint32. Esempi: Chiller Local/Remote all'indirizzo 0 (FC 3, uint16); Chiller Enable Output all'indirizzo 1 (FC 3, uint16); Run Enabled all'indirizzo 2 (FC 3, uint16); Chiller Capacity Limited all'indirizzo 3 (FC 3, uint16).
HVACDa documento
Mappa registri Modbus
10 registri
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
| Len | Scala | Endian | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 0 | Chiller Local/Remote Set at the keypad only; Local makes the controller ignore network commands. | chiller_local_remote | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 1 | Chiller Enable Output | chiller_enable_output | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 2 | Run Enabled Chiller may start if operating conditions allow. | run_enabled | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 3 | Chiller Capacity Limited | chiller_capacity_limited | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 4 | Alarm Digital Output Poll this for any active alarm. | alarm_digital_output | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 5 | Evaporator Flow Switch Status | evaporator_flow_switch_status | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 7 | Chiller On/Off | chiller_on_off | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 8 | Chiller Enable Setpoint Network enable; Null behaves as Disable. | chiller_enable_setpoint | 3 | uint16 | 1 | 1 | — | R/W | big_word_swap | |
| 9 | Clear Alarms - Network Some lockout alarms cannot be cleared from the network. | clear_alarms_network | 3 | uint16 | 1 | 1 | — | R/W | big_word_swap | |
| 10 | Chiller Mode Output | chiller_mode_output | 3 | uint16 | 1 | 1 | — | R | big_word_swap |
Stai vedendo 10 registri su 96.
La mappa completa è riservata agli utenti registrati. La registrazione è gratuita.