manufacturer: socomec
model: STATYS (STS)
device: STATYS (STS)
category: Altro
protocol: modbus
version: v1
firmware: null
verification: IMPORTED
isDemo: false
source:
  title: Import PDF
    NET-VISION-8.3_INSTALLATION-AND-OPERATING-MANUAL_2025-03_552370E_EN_0.pdf
  url: null
  documentRef: null
  revision: null
generatedAt: 2026-09-21T13:21:32.702Z
registers:
  - address: "256"
    addressNumeric: 256
    signal: sts_reference
    name: STS reference
    description: DIM=10 (ASCII).
    functionCode: 3
    datatype: string
    length: null
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "278"
    addressNumeric: 278
    signal: sts_serial_number
    name: STS serial number
    description: DIM=10 (ASCII).
    functionCode: 3
    datatype: string
    length: null
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "288"
    addressNumeric: 288
    signal: config_0x0120
    name: CONFIG (0x0120)
    description: DIM=16. Nessuna scomposizione per campo fornita dal documento originale.
    functionCode: 3
    datatype: string
    length: null
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "320"
    addressNumeric: 320
    signal: status_0x0140
    name: STATUS 0x0140
    description: bit0=Source 1 OK; bit1=Source 1 critical; bit2=Source 1 out of
      tolerance; bit3=Source 1 absent; bit4=Power Path 1 OK; bit5=(riservato);
      bit6=Source 2 OK; bit7=Source 2 critical; bit8=Source 2 out of tolerance;
      bit9=Source 2 absent; bit10=Power Path 2 OK; bit11=(riservato);
      bit12=Sources perm. Synchronised; bit13=Sliding Sources; bit14=Sources
      perm. Not Synchron.; bit15=Sources Instant. Synchron.
    functionCode: 3
    datatype: bitfield
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "321"
    addressNumeric: 321
    signal: status_0x0141
    name: STATUS 0x0141
    description: bit0=S1 is preferred source; bit1=Load on preferred source;
      bit2=Load on alternate source; bit3=Load not supplied; bit4=Load on manual
      by-pass1; bit5=Load on manual by-pass2; bit6=(riservato); bit7=Load on S1;
      bit8=Load on S2; bit9=(riservato); bit10=Transfer locked ext.;
      bit11=(riservato); bit12=Output OK; bit13=Output out of tolerance;
      bit14=Output absent; bit15=(riservato).
    functionCode: 3
    datatype: bitfield
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "322"
    addressNumeric: 322
    signal: status_0x0142
    name: STATUS 0x0142
    description: "bit0=ESD input active; bit1=Q41 closed; bit2=Q42 closed; bit3=SS1
      closed; bit4=SS2 closed; bit5=Q30 closed; bit6=Q51 closed; bit7=Q52
      closed; bit8-12=(riservato); bit13=Remote controls enabled;
      bit14=Maintenance alert; bit15=User mode. Nota: la tabella riepilogativa
      del documento dichiara il blocco STATUS come 4 parole (0x0140-0x0143), ma
      il dettaglio dei bit copre solo queste 3 parole: la quarta (0x0143) non e'
      documentata nel manuale e non e' importata."
    functionCode: 3
    datatype: bitfield
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "328"
    addressNumeric: 328
    signal: alarms_0x0148
    name: ALARMS 0x0148
    description: bit0=Imminent stop; bit1=Output Isc detection; bit2=Manual By-Pass;
      bit3=Overload; bit4=SoLink Alarm; bit5=Consecutive Detections;
      bit6=Switchback impossible; bit7=Transfer impossible; bit8=(riservato);
      bit9=PowerPath1 deteriorated; bit10=PowerPath1 short circuit;
      bit11=PowerPath1 in failure; bit12=(riservato); bit13=PowerPath2
      deteriorated; bit14=PowerPath2 short circuit; bit15=PowerPath2 in failure.
    functionCode: 3
    datatype: bitfield
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "329"
    addressNumeric: 329
    signal: alarms_0x0149
    name: ALARMS 0x0149
    description: bit0=Backfeed1 protection open; bit1=Backfeed2 protection open;
      bit2=Ambient temperature max; bit3-8=(riservato); bit9=Preventive Alarm;
      bit10=Wrong Configuration; bit11=HMI Alarm; bit12=Electronics alarm;
      bit13=Custom input alarm; bit14=Maintenance alarm; bit15=General Alarm.
    functionCode: 3
    datatype: bitfield
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "544"
    addressNumeric: 544
    signal: s1_voltage_l1n
    name: S1 voltage L1N
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "545"
    addressNumeric: 545
    signal: s1_voltage_l2n
    name: S1 voltage L2N
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "546"
    addressNumeric: 546
    signal: s1_voltage_l3n
    name: S1 voltage L3N
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "547"
    addressNumeric: 547
    signal: s1_voltage_u12
    name: S1 voltage U12
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "548"
    addressNumeric: 548
    signal: s1_voltage_u23
    name: S1 voltage U23
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "549"
    addressNumeric: 549
    signal: s1_voltage_u31
    name: S1 voltage U31
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "550"
    addressNumeric: 550
    signal: s1_frequency
    name: S1 frequency
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: Hz
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "551"
    addressNumeric: 551
    signal: ss1_temperature
    name: SS1 temperature
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: °C
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "552"
    addressNumeric: 552
    signal: s2_voltage_l1
    name: S2 voltage L1
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "553"
    addressNumeric: 553
    signal: s2_voltage_l2
    name: S2 voltage L2
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "554"
    addressNumeric: 554
    signal: s2_voltage_l3
    name: S2 voltage L3
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "555"
    addressNumeric: 555
    signal: s2_voltage_u12
    name: S2 voltage U12
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "556"
    addressNumeric: 556
    signal: s2_voltage_u23
    name: S2 voltage U23
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "557"
    addressNumeric: 557
    signal: s2_voltage_u31
    name: S2 voltage U31
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "558"
    addressNumeric: 558
    signal: s2_frequency
    name: S2 frequency
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: Hz
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "559"
    addressNumeric: 559
    signal: ss2_temperature
    name: SS2 temperature
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: °C
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "560"
    addressNumeric: 560
    signal: output_voltage_l1
    name: Output voltage L1
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "561"
    addressNumeric: 561
    signal: output_voltage_l2
    name: Output voltage L2
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "562"
    addressNumeric: 562
    signal: output_voltage_l3
    name: Output voltage L3
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "563"
    addressNumeric: 563
    signal: output_voltage_u12
    name: Output voltage U12
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "564"
    addressNumeric: 564
    signal: output_voltage_u23
    name: Output voltage U23
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "565"
    addressNumeric: 565
    signal: output_voltage_u31
    name: Output voltage U31
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: V
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "566"
    addressNumeric: 566
    signal: output_frequency
    name: Output frequency
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: Hz
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "568"
    addressNumeric: 568
    signal: output_current_i1
    name: Output current I1
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "569"
    addressNumeric: 569
    signal: output_current_i2
    name: Output current I2
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "570"
    addressNumeric: 570
    signal: output_current_i3
    name: Output current I3
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "571"
    addressNumeric: 571
    signal: output_current_in
    name: Output current IN
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "573"
    addressNumeric: 573
    signal: output_load_rate
    name: Output load rate
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: "%"
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "575"
    addressNumeric: 575
    signal: s1_s2_phase_shift
    name: S1-S2 phase shift
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: °
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "576"
    addressNumeric: 576
    signal: output_apparent_p_l1
    name: Output Apparent P. L1
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: kVA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "577"
    addressNumeric: 577
    signal: output_apparent_p_l2
    name: Output Apparent P. L2
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: kVA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "578"
    addressNumeric: 578
    signal: output_apparent_p_l3
    name: Output Apparent P. L3
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: kVA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "579"
    addressNumeric: 579
    signal: output_power_factor_l1
    name: Output Power factor L1
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "580"
    addressNumeric: 580
    signal: output_power_factor_l2
    name: Output Power factor L2
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "581"
    addressNumeric: 581
    signal: output_power_factor_l3
    name: Output Power factor L3
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "584"
    addressNumeric: 584
    signal: output_crest_factor_l1
    name: Output crest factor L1
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "585"
    addressNumeric: 585
    signal: output_crest_factor_l2
    name: Output crest factor L2
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "586"
    addressNumeric: 586
    signal: output_crest_factor_l3
    name: Output crest factor L3
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "587"
    addressNumeric: 587
    signal: output_crest_factor_n
    name: Output crest factor N
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "591"
    addressNumeric: 591
    signal: ambient_temperature
    name: Ambient temperature
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: °C
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "592"
    addressNumeric: 592
    signal: output_active_power_l1
    name: Output Active Power L1
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: kW
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "593"
    addressNumeric: 593
    signal: output_active_power_l2
    name: Output Active Power L2
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: kW
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "594"
    addressNumeric: 594
    signal: output_active_power_l3
    name: Output Active Power L3
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: kW
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "595"
    addressNumeric: 595
    signal: global_active_power
    name: Global Active Power
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: kW
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "600"
    addressNumeric: 600
    signal: output_load_rate_l1
    name: Output load rate L1
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: "%"
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "601"
    addressNumeric: 601
    signal: output_load_rate_l2
    name: Output load rate L2
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: "%"
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "602"
    addressNumeric: 602
    signal: output_load_rate_l3
    name: Output load rate L3
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: "%"
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "603"
    addressNumeric: 603
    signal: output_load_rate_n
    name: Output load rate N
    description: "Nessuna tabella di scala/formato esplicita per questo blocco nel
      documento originale (a differenza del mapping VU-MAP): riportato a scala 1
      (valore grezzo)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 1
    offset: 0
    unit: "%"
    access: READ
    endianness: null
    group: null
    notes: null